UPSMON User Manual Troubleshooting 83
Please print out the help documents with ”man termadd”. All options are stored for this command. With
”termdel” this port is deleted. With ”termshow grep UPS” the configuration can be displayed.
f. Using SCO-computer systems a terminal translator (mapchan or mapkey) may be mapped on the
configured tty port with /etc/default/mapchan (in most cases only on com1/ttya). This causes a malfunction
of the RS 232-port. Check if this process is active and delete it if necessary. Check in the file /etc/gettydefs,
which baud rate has been assigned to the port and change it to correspond to the UPS-parameter.
g. HP UNIX computers sometimes have the following entry in the inittab: ups0:: respawn:rtprio 0
/usr/ups_mond -f /etc/ups_conf. In the SAM menu Peripheral Devices > Uninterruptible Power Supplies
this entry is to be found, but not activated. But this causes the device not to work correctly with UPSMON.
Delete this entry and restart.